The 4CX185SQMM XLPE/PVC Aluminum Conductor Armoured Cable is engineered to meet high safety standards and performance requirements, making it an ideal choice for industrial and infrastructural electrical installations. Compliant with IS 7098 and IS 8130 standards, this cable is designed to operate at a voltage of up to 1100V with permissible voltage and frequency variations of ±10%. The core consists of H2 grade aluminum wires arranged in a stranded and shaped formation, ensuring reduced resistance and improved conductivity. With an insulation made from high-quality XLPE compounds, this cable guarantees thermal stability, superior dielectric properties, and enhanced resistance to moisture and chemicals. This cable is robust, featuring a galvanized steel strip armoured layer that enhances its durability and protection in harsh environments. The outer sheath made of extruded PVC provides further insulation and resilience against external factors, ensuring longevity and reliability for any electrical application.
Key Features
Features | Description |
---|---|
Conductor Material | H2 Grade Aluminum Wire (Class-2) |
Operating Voltage | 1100 V |
Insulation Material | XLPE Compound |
Outer Sheath Material | Extruded PVC Type ST-2 |
Armouring Material | Galvanized Steel Strip |
Current Rating in Air | 329 Amperes |
Minimum Bending Radius | 12 x D |
High Voltage Test | 3 KV (rms) for 5 Minutes |
Attributes | Description |
---|---|
Conductor Resistance (Max at 20°C) | 0.164 Ohm/KM |
Conductor Resistance (Max at 90°C) | 0.210 Ohm/KM |
Inner Sheath Thickness (Min) | 0.5 mm |
Outer Sheath Thickness (Min) | 2.04 mm |
Overall Diameter of Cable | 48 mm (+/-2.0 mm) |
Standard Length | 500 m (±5%) |
Minimum Volume Resistivity | 1 x 10^14 Ω-CM at 27 °C |
Maximum Operating Temp. | 90 °C |
Short Circuit Current Rating for 1 Sec. | 17.5 kA |
Cable Code | A2XFY |
Key Words
*Disclaimer: This above description has been AI generated and has not been audited or verified for accuracy. It is recommended to verify product details independently before making any purchasing decisions.
Brand: AURAFLEX
Country of Origin: India
SPECIFICATION IS:7098/PART-1/1988 ,IS 8130/1984,IS 5831 WITH LATEST AMENDMENTS &THIS DATASHEET
OPERATING VOLTAGE 1100 V
PERMISSIBLE VARIATION VOLTAGE & FREQUENCY ±10 %
CONDUCTOR DETAIL CONDUCTOR DETAIL
MATERIAL H2 GRADE ALUMINIUM WIRE (CLASS-2) ASPER IS 8130/1984
SIZE SQMM (MAIN&NEUTRAL) 185
SHAPE OF CONDUCTOR STRANDED & SHAPED
CONDUCTOR RESISTANCE OHM/KM (MAX) AT 20 ⁰C (MAIN&NEUTRAL) 0.164
CONDUCTOR RESISTANCE OHM/KM (MAX) AT 90 ⁰C (MAIN&NEUTRAL) 0.210
INSULATION INSULATION
MATERIAL XLPE COMPOUND AS PER IS 7098/1988
THICKNESS NOM. MM (MAIN&NEUTRAL) 1.60
THICKNESS MIN. MM (MAIN&NEUTRAL) 1.16
COLOUR OF CORE RED, YELLOW , BLUE & BLACK
INNER SHEATH
MATERIAL EXTRUDED PVC TYPE ST-2 COMPOUND
THICKNESS OF INNER SHEATH (MM /MIN ) 0.5
COLOUR OF INNER SHEATH BLACK
ARMOURING ARMOURING
MATERIAL GALVANIZED STEEL STRIP
DIMENSION MM. 4.0X0.80MM+/-10 %
OUTER SHEATH OUTER SHEATH
MATERIAL EXTRUDED PVC TYPE ST-2 COMPOUND
THICKNESS OF OUTER SHEATH (NOMINAL) MM NA
THICKNESS OF OUTER SHEATH (MIN) MM 2.04
COLOUR OF SHEATH
OVERELL DIAMETER OF CABLE (+/-2.0 MM) 48
STANDARD LENGTH (±5%) 500 (mtr)
PACKING NON REFUNDABLE WOODEN DRUMS IS:10418/82
MIN. VOLUME RESISTIVITY (MIN) 1 x 1014 Ω-CM AT 27 oC & 1 x 1012 Ω-CM AT 90 oC
HIGH VOLTAGE TEST 3 KV (rms) FOR 5 MINUTES FOR EACH CONNECTION
MINIMUM BENDING RADIUS 12 X D
MAXIMUM OPERATING TEMP. 90 ⁰C
MAXIMUM CONDUCTOR TEMPERATURE DURING SHORT CIRCUIT 250 ⁰C
CURRENT RATING
IN GROUND 282
IN AIR 329
SHORT CIRCUIT CURRENT RATING FOR 1 SEC. DURATION 17.5
CABLE CODE A2XFY
Inclusive of all taxes
You Save: 0.00